Chapter 6. LIST OF DISPLAYS AND SETTING DATA
■
Parameter bank
Bank selection:
Display
Item
Contents
Initial
value
User
level
Remarks
Control method
0: ON/OFF control
1: Fixed PID
0
or
1
0
The initial value is “0” when
the control output uses only
one point and is the relay
output. The initial value is “1”
in other cases.
MV low limit at AT
-10.0 to +110.0%
0.0
0
Displayed when the control
method is other than the
ON/OFF control (CtrL
≠
0).
MV high limit at AT
-10.0 to +110.0%
100.0
0
Differential
(for ON/OFF control)
0 to 9999U
5
0
Displayed when the control
method is the ON/OFF
control (CtrL=0).
ON/OFF control
action point offset
-1999 to +9999U
0
2
PV filter
0 to 120.0s
0.0
0
PV ratio
0.001 to 9.999
1.000
1
PV bias
-1999 to +9999U
0
0
Time proportional
cycle unit 1
(for MV1)
0: 1s unit
1: Cycle fixed at 0.5s.
2: Cycle fixed at 0.25s.
3: Cycle fixed at 0.1s
If the set value is other than “0”, the
time proportional cycle 1 (Cy) cannot
be set.
0
2
Time proportional
cycle 1
(for MV1)
5 to 120s (Output destination of MV1
includes the relay output.)
1 to 120s (Output destination of MV1
does not include the relay output.)
If the time proportional unit 1 (CyU)
≠
0, this setting becomes invalid and
the setting becomes impossible.
10
or
2
0
Time proportional
cycle unit 2
(for MV2)
0: 1s unit
1: Cycle fixed at 0.5s.
2: Cycle fixed at 0.25s.
3: Cycle fixed at 0.1s
If the set value is other than “0”, the
time proportional cycle 2 (Cy2)
cannot be set.
0
2
Time proportional
cycle 2
(for MV2)
5 to 120s (Output destination of MV2
includes the relay output.)
1 to 120s (Output destination of MV2
does not include the relay output.)
If the time proportional unit 2 (CyU2)
≠
0, this setting becomes invalid and
the setting becomes impossible.
10
or
2
0
RSP filter
0.0 to 120.0s
0.0
0
Displayed when the model
provides the RSP input.
RSP ratio
0.001 to 9.999
1.000
1
RSP bias
-1999 to +9999U
0
0
Summary of Contents for SDC35
Page 16: ......
Page 17: ......
Page 19: ... display key para key or V key key enter key 2 second press hold of para key V ...
Page 32: ......
Page 46: ......
Page 58: ......
Page 71: ......
Page 84: ......
Page 95: ......
Page 172: ......
Page 174: ...6 2 Chapter 6 LIST OF DISPLAYS AND SETTING DATA ...
Page 211: ......
Page 230: ......
Page 240: ......
Page 248: ......
Page 260: ......
Page 268: ......
Page 270: ......
Page 279: ......