![Yamatake SDC35 User Manual Download Page 102](http://html.mh-extra.com/html/yamatake/sdc35/sdc35_user-manual_905228102.webp)
■
STEP PV start
Whether or not the PV start exists and its type at start of the step operation can be
set.
• When this setting is set at “0”, the step operation is started from the SOAK
portion of step 1.
• When this setting is set at “1”, the step operation is started from the same SP as
PV in the up RAMP portion of step 1 if PV<SP-1. If PV
≥
SP-1, the step
operation is started from the SOAK portion of step 1.
• When this setting is set at “2”, the step operation is started from the same SP as
PV in the down RAMP portion of step 1 if PV>SP-1. If PV
≤
SP-1, the step
operation is started from the SOAK portion of step 1.
5-44
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
Item (Bank)
Display
Contents
Initial value
User level
STEP PV start
(Setup bank)
0: None
1: Up start
2: Down start
0