5-107
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
5 - 14 Position Proportional Control
When the control output type of the model is R1 (motor drive relay output), the position proportional control is
performed. In the position proportional control, the ON/OFF control of the relays on the open and close sides is
performed so that the MV (manipulated variable) by the PID control, MANUAL operation, and output at READY
meets the opening (MFB) of the modutrol motor.
■
Position proportional type
• On position proportional control models (with code R1 in the control output
segment of the model No.), the factory setting for At-d (AT derivative time
adjustment coefficient) in the Extended tuning bank is 0.00, and therefore the
derivative time is 0 seconds when AT is complete. To have the AT result affect
control, change the At-d setting to 1.00 and re-execute AT. For details, refer to:
• When the control output type is R1 (motor drive relay output), the Heat/Cool
control is not enabled.
• When the control output type is R1 (motor drive relay output), the display and
setting can be performed.
• In case of the position proportional control model, the Heat/Cool control is not
enabled.
Handling Precautions
• When [C57: Position proportional type] is set to [0: MFB c
Estimated position control] or [1: MFB control], set [C60: Motor auto
adjust] to [1: Start] and execute the motor auto adjust. For details,
refer to;
the motor auto adjust, refer to
Motor auto adjust ( on page 5-109 ).
When [C57: Position proportional type] is set to [2: Estimated position
control (MFB disabled)] or [3: Estimated position control (MFB
disabled) + Position adjustment at power ON], set the precise value to
[C63: Motor full close-full open time].
●
Setting 0 (MFB c Estimated position control)
When the Motor Feed Back (MFB) input is correct, the motor position is
controlled by actually measured MFB.
When using this setting, the setup (C60) is set at “1” to perform the motor auto
adjust.
• If the MFB input is faulty, the motor position is controlled by the estimated MFB
value. This status is called “estimated position control status”.
For example, if the motor is rotated to the position where the feedback
potentiometer deteriorates, the MFB input is changed rapidly.
This rapid change is detected as error to estimate the correct MFB position.
Additionally, if the MFB burnout alarm occurs, the motor position is also
controlled by the estimated MFB value.
Item (Bank)
Display
Contents
Initial value
User level
Position proportional type
(Setup bank)
0: MFB control and Estimated position control
1: MFB control
2: Estimated position control (MFB disabled)
3: Estimated position control (MFB disabled) +
Position adjustment at power ON.
0
Basic,
Standard,
High function
Summary of Contents for SDC35
Page 16: ......
Page 17: ......
Page 19: ... display key para key or V key key enter key 2 second press hold of para key V ...
Page 32: ......
Page 46: ......
Page 58: ......
Page 71: ......
Page 84: ......
Page 95: ......
Page 172: ......
Page 174: ...6 2 Chapter 6 LIST OF DISPLAYS AND SETTING DATA ...
Page 211: ......
Page 230: ......
Page 240: ......
Page 248: ......
Page 260: ......
Page 268: ......
Page 270: ......
Page 279: ......