8 - 3
Description of Commands
■
Read command (03H)
●
Send Message
This is a command capable of reading the contents of continuous data addresses
from a specified read start data address with a single message. The following is an
example of send message while reading data:
MODBUS ASCII
(1) Start of message
(2) Station address
(3) Read command
(4) Start data address
(5) Number of read data
(6) Checksum (LRC)
(7) Delimiter
MODBUS RTU
(1) Station address
(2) Read command
(3) Start data address
(4) Number of read data
(5) Checksum (CRC)
●
Response Message
A response message corresponding to the command content is returned when the
message is correctly received.
The figure below shows the structure of the response message while reading data.
MODBUS ASCII
• Example in case of normal reception
(1) Start of message
(2) Station address
(3) Read command
(4) Number of read data X 2
(5) Read data 1
(6) Read data 2
(7) Checksum (LRC)
(8) Delimiter
8-7
Chapter 8. MODBUS COMMUNICATION FUNCTION
(2)
(1)
(3)
(4)
3AH
:
30H
0
41H
A
30H
0
33H
3
30H
0
33H
3
45H
E
39H
9
30H
0
30H
0
30H
0
32H
2
30H
0
35H
5
0DH
CR
0AH
LF
(5)
(6)
(7)
(2)
(1)
(3)
(4)
0AH 03H 03H E9H 00H 02H 14H
(5)
C0H
(2)
(1)
(3)
(4)
3AH
:
30H
0
41H
A
30H
0
33H
3
30H
0
34H
4
30H
0
33H
3
30H
0
31H
1
30H
0
30H
0
30H
0
33H
3
45H
E
38H
8
D0H
CR
0AH
LF
(5)
(6)
(7)
(8)
Summary of Contents for SDC35
Page 16: ......
Page 17: ......
Page 19: ... display key para key or V key key enter key 2 second press hold of para key V ...
Page 32: ......
Page 46: ......
Page 58: ......
Page 71: ......
Page 84: ......
Page 95: ......
Page 172: ......
Page 174: ...6 2 Chapter 6 LIST OF DISPLAYS AND SETTING DATA ...
Page 211: ......
Page 230: ......
Page 240: ......
Page 248: ......
Page 260: ......
Page 268: ......
Page 270: ......
Page 279: ......