![Yamatake SDC35 User Manual Download Page 136](http://html.mh-extra.com/html/yamatake/sdc35/sdc35_user-manual_905228136.webp)
5-78
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
5 - 10
Application Examples
This section describes examples of applications using the assignment functions of this unit.
■
Examples of applications using assignment functions
The following shows setting examples with the
SLP-C35
Smart Loader Package.
To use assignment functions, it is absolutely necessary to set the user level to
“High function configuration”.
●
Example 1 Logical OR of the heater burnout and PV high limit alarm is output.
Conditions: PV high limit is set to Internal Event 1.
Heater burnout is set to Internal Event 2.
Logical OR of the above events is output to the EV1 relay.
(1) Select
[Standard]
→
[Event]
and set
[Internal Event 1]
to
[1: PV high limit]
.
(2) Similarly, set
[Internal Event 2]
to
[16: Heater 1 break/Heater over
current]
.
(3) Select
[Option]
→
[DO Assignment]
and right-click on the operation type of
[Event output 1]
to select
[Input/Output port setup]
.
Summary of Contents for SDC35