Chapter 6. LIST OF DISPLAYS AND SETTING DATA
Display
Item
Contents
Initial
value
User
level
Remarks
Motor long life mode
0: Aiming at controllability
1: Aiming at service life of
potentiometer
1
0
Input with motor fully
open
0 to 9999
3000
0
Motor full close-full
open time
5.0 to 240.0s
30.0
0
AUX range type
Same as control output 1.
1
0
Displayed when the auxiliary
output of the model is the
current output or continuous
voltage output.
The decimal point position
and unit is the same as that
of the control output 1.
AUX type
3
0
AUX Value at 0%
output
-1999 to +9999 (The decimal point
position and unit may vary depending
on the AUX type.)
0
0
AUX Value at 100%
output
1000
0
Position proportional
type
0: MFB c Estimated position
control
1: MFB control
2: Estimated position control (MFB
disabled)
3: Estimated position control (MFB
disabled) + Position adjustment at
power ON.
0
0
Position proportional
dead zone
0.5 to 25.0%
10.0
0
Motor auto adjust
0: Stop
1: Start
0
0
Displayed when the model
provides the position
proportional output.
The motor adjust is stopped
using the [disp] or [mode] key
through the control operation.
It is impossible to write data
through the loader.
Input with motor fully
closed
0 to 9999
1000
0
Displayed when the model
provides the position
proportional output.
It is impossible to write data
through the loader.
Station address
0 to 127
(Communication is disabled when set
at "0".)
0
0
CPL/MODBUS
0: CPL
1: MODBUS (ASCII format)
2: MODBUS (RTU format)
0
0
Displayed when the optional
model has RS-485.
(Continue on next page.)
Displayed when the model
provides the position
proportional output.
Control output 2
range
Same as control output 1.
1
0
Control output 2 type
3
0
Control output 2
scaling low limit
-1999 to +9999
The decimal point position and unit
may vary depending on control
output 2 type.
0
0
Displayed when control
output 2 of the model is the
current output or continuous
voltage output.
The decimal point position
and unit is same as that of
control output 1.
Control output 2
scaling high limit
1000
0
Control output 2 MV
scaling range
200.0
0
0 to 9999
The decimal point position and unit
are same as for PV.
If the controller model uses
current output for control
output 2 and if the control
output 2 type is SP+MV or
PV+MV, this setting is
displayed.
Auxiliary output MV
scaling range
200.0
0
0 to 9999
The decimal point position and unit
are same as for PV.
If the controller model uses
current output for the
auxiliary output and if the
auxiliary output type is
SP+MV or PV+MV, this
setting is displayed.
Summary of Contents for SDC35
Page 16: ......
Page 17: ......
Page 19: ... display key para key or V key key enter key 2 second press hold of para key V ...
Page 32: ......
Page 46: ......
Page 58: ......
Page 71: ......
Page 84: ......
Page 95: ......
Page 172: ......
Page 174: ...6 2 Chapter 6 LIST OF DISPLAYS AND SETTING DATA ...
Page 211: ......
Page 230: ......
Page 240: ......
Page 248: ......
Page 260: ......
Page 268: ......
Page 270: ......
Page 279: ......