5-4
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
■
PV square root extraction dropout
When the PV input range type is DC voltage or DC current, a dropout value can be
set so that the result of the PV square root extraction used to convert the pressure
(differential pressure) into the flow becomes "0".
• When the PV input range type is DC voltage or DC current, the display and
setting can be made.
• Details of PV square root extraction
The calculation input in % and the calculation result in % are expressed as PVin
and PVout, respectively.
When the PV input is the PV square root extraction dropout set value or more
and less than 100.0%, the control formula becomes as shown below.
PVout =
√
PVin/100
X
100
When the PV input is larger than 0.0% and smaller than the PV square root
extraction dropout set value, PVout = 0.0%.
When the PV input is 0.0% or less or 100.0% or more, the square root extraction
is not performed. Therefore, PVout = PVin.
Item (Bank)
Display
Contents
Initial value
User level
PV square root extraction
dropout
(Setup bank)
0.0%: Square root extraction is not performed.
0.1 to 100.0%
0.0%
High function
Output after PV square root extraction (PVout)
100%FS
PVin
Dropout value (variable change from 0.1 to 100.0%)
0
100%FS
0
Y = Xin/100 X100
Summary of Contents for SDC35
Page 16: ......
Page 17: ......
Page 19: ... display key para key or V key key enter key 2 second press hold of para key V ...
Page 32: ......
Page 46: ......
Page 58: ......
Page 71: ......
Page 84: ......
Page 95: ......
Page 172: ......
Page 174: ...6 2 Chapter 6 LIST OF DISPLAYS AND SETTING DATA ...
Page 211: ......
Page 230: ......
Page 240: ......
Page 248: ......
Page 260: ......
Page 268: ......
Page 270: ......
Page 279: ......