11-5
Chapter 11. CALIBRATION
●
Current Transformer (CT) input calibration
(1) Select the
[CT input calibration]
tab.
(2) Select a desired channel to be calibrated.
(3) Select
[Zero]
from the zero span selection items.
(When selecting a channel, perform the [
Zero]
calibration first, and then
perform the
[Span]
calibration next since “Zero/Span” is set for one channel.)
(4) Click
[Read]
.
(5) A current value of “0” is applied to the CT input terminal of the channel you
have selected and keep the apply status for approximately 30 sec. For details
about how to connect measuring instruments in the apply status, refer to the
following Figures:
(6) Click
[Write]
.
(7) Select
[Span]
from the zero span selection items.
(8) Click
[Read
].
(9) Apply a span current value to the CT input terminal of the channel you have
selected and keep the apply status for approximately 30s.
(10) Click
[Write]
.
(11) If any channels to be calibrated remain, return to operation step (2).
Handling Precautions
To calibrate the CT input, connect the DC current (mA) to the input
terminal.
Current
generator
CT input 1
This unit
-
+
(7)
(8)
(9)
Current
generator
CT input 2
This unit
-
+
(7)
(8)
(9)
Summary of Contents for SDC35
Page 16: ......
Page 17: ......
Page 19: ... display key para key or V key key enter key 2 second press hold of para key V ...
Page 32: ......
Page 46: ......
Page 58: ......
Page 71: ......
Page 84: ......
Page 95: ......
Page 172: ......
Page 174: ...6 2 Chapter 6 LIST OF DISPLAYS AND SETTING DATA ...
Page 211: ......
Page 230: ......
Page 240: ......
Page 248: ......
Page 260: ......
Page 268: ......
Page 270: ......
Page 279: ......