118 •
750-671 [Steppercontroller]
Advanced
Diagnostics
WAGO-I/O-SYSTEM
750
I/O
Modules
The Trace_Stored bit indicates that a complete data set has been recorded.
A 0
1 edge of Trace_Trigger initiates recording when the Trace_Armed bit
is set.
A traced (recorded) data set can be read out using an upload command from
the table manager (see Table Manager).
Bits
deleted
set
Trace_Stored
Data set not yet available
a data set has been saved
Trace_Trigger 0
1 edge starts recording
Trace_Armed Triggering
is
blocked; an existing
data set is not overwritten
Triggering active; recording is
started by the next triggering event
The internal bits (see Chapter 3.4, „Bit field for I/O driver“) can be used as
triggering sources. This is accomplished by entering the corresponding link in
the configuration table. The control system can also initiate recording using
the mailbox commands GET_BIT and SET_BIT. The trigger bits must be
linked to the MONE internal bit for this.