![WAGO I/O SYSTEM 750 750-671 Manual Download Page 200](http://html1.mh-extra.com/html/wago/i-o-system-750-750-671/i-o-system-750-750-671_manual_3328297200.webp)
200 •
Reference Commands for Move Mode
Auxiliary
Commands
WAGO-I/O-SYSTEM
750
I/O
Modules
3.2.4.4.6
GOTO_IF (0xF6)
If a bit has been set, table processing is continued at the addressed entry;
otherwise the next table entry is used.
Command number range: 1 … 500
Request
Byte 2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
MB0
0x40
MB1 T
-
MB2
0xF6
MB3
Number of next command (LSB)
MB4
Number of next command (MSB)
MB5
Number of bit to be checked
Response
Byte 2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
MB0
0x40
MB1 T
Return
Code
MB2
0xF6
MB3 Reserved
MB4 Reserved
MB5 Reserved