154 •
Reference Commands – Mailbox Commands
Position table commands
WAGO-I/O-SYSTEM
750
I/O
Modules
3.1.4.7.3
POS_TABLE_WR (0x5E)
Writes an entry to the active position table. The table index that was last set
using POS_TABLE_SET_PTR is always overwritten.
Request
Byte 2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
MB0
0x5E
MB1 T
-
MB2
Save value (LSB)
MB3 Save
value
MB4 Save
value
MB5
Save value (MSB)
Response
Byte 2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
MB0
0x5E
MB1
T
Return Code
MB2 Status
MB3 Reserved
MB4 Reserved
MB5 Reserved
0x00: OK
Return
Code
0x37:
Table does not exist, or index not set
0:
Writing completed successfully
Status
1: Writing
aborted