Overview of Error Blink Codes
•
209
Auxiliary
Commands
WAGO-I/O-SYSTEM 750
I/O Modules
Error
No.
Name
Description
Possible cause/Remedy
1241 IO_BITINDEX
TOLARGE
Access to non-available
bit (internal)
Configuration, check Move
program and Mailbox
commands for incorrect bit
addresses
1242 IO_ILLEGAL_
USERBITNR
Bit can not be modified
by user
An attempt was made to
change a bit not linked to
MZERO or MONE using
the Move program of
Mailbox command
1243 IO_USERBIT_
READONLY
Bit can not be written
Bit not authorized for
external write access
1245 IO_RECURSIVE_
LINK
Excessive nesting for
linked bit
A linkable bit was linked to
a linkable bit that was
linked to a linkable bit; a
linkable bit may be linked
to itself.
1246 IO_TIMER_1
Configuration: Filter
function not defined
Check configuration for
filter functions
1247 IO_UNKNOWN_
TIMER
Filter with this number
not available
Check configuration for
filter functions
1248 IO_TIMERMODE Filter function does not
permit write access
The current filter function
configuration does not
permit writing of the filter
1249 IO_BITNOT
IMPLEMENTED
Requested bit not
implemented (internal)
A bit being used can not be
queried (internal error)
1311 TBL_PROGRAM_
STOP1
Move program
terminated with error
message 1
Check the termination
condition of the Move
program
1312 TBL_PROGRAM_
STOP2
Move program
terminated with error
message 2
Check the termination
condition of the Move
program
1313 TBL_PROGRAM_
STOP3
Move program
terminated with error
message 3
Check the termination
condition of the Move
program
1314 TBL_PROGRAM_
STOP4
Move program
terminated with error
message 4
Check the termination
condition of the Move
program
1315 TBL_PROGRAM_
STOP5
Move program
terminated with error
message 5
Check the termination
condition of the Move
program
1316 TBL_PROGRAM_
STOP6
Move program
terminated with error
message 6
Check the termination
condition of the Move
program