Overview of Error Blink Codes
•
233
Auxiliary
Commands
WAGO-I/O-SYSTEM 750
I/O Modules
Bit number
Default
Name
Dec.
Hex.
Type
Target/Source Bit no.
Description
Save setpoints from Module 2.2 and, where
applicable, calculate a movement sequence in
advance.
0:
Each setpoint that is transmitted via
cyclic telegram traffic must be accepted
and processed. Any precalculated
movement sequence is rejected. A
movement sequence can be calculated
and started using Start.
PreCalc 189
0xBD
DST/
SRC
KBUS_CTRL2
_6
0x4E
1:
The setpoints from the cyclic telegram
traffic are ignored and the setpoint saved
for the 0
1 edge used instead. If the
starting speed is zero, a movement
sequence will be calculated in advance
using this setpoint; this sequence can
then be started with the normal delay
using Start.
Setup mode selected.
When the bit SetupSpeed_Active_ACK is set
the drive speed is limited to the defined setup
speed.
0:
Setup mode not selected.
Setup_
Speed_Active
190 0xBE DST/
SRC
KBUS_CTRL3
_6
0x56
1:
Setup mode selected.
Error_Quit 191
0xBF
DST/
SRC
KBUS_CTRL2
_7
0x4F Acknowledge
error.
All errors that are present are acknowledged at
the rising edge from 0 to 1. After
acknowledgement, the error switches to 0, or a
new error is present.
Limit switch input on movement in positive
direction.
This bit is linked to the internal bus.
0:
The positive direction limit switch is not
actuated.
LimitSwitch_
Pos
192 0xC0 DST/
SRC
KBUS_CTRL3
_4
1:
The positive direction limit switch is
actuated. The drive is being run down.