Overview of Error Blink Codes
Auxiliary
Commands
WAGO-I/O-SYSTEM
750
I/O
Modules
Error
No.
Name
Description
Possible cause/Remedy
1565
MCALC_DIST1
Internal range exceeded
for movement path
internal *
1566
MCALC_DIST2
Internal range exceeded
for movement path
internal *
1567
MCALC_DIST3
same as PARTMODL_
POSITION_RANGE
same as PARTMODL_
POSITION_RANGE
1568
MCALC_DIST4
Internal range exceeded
for movement path
internal *
1569
MCALC_DIST5
same as PARTMODL_
POSITION_RANGE
same as PARTMODL_
POSITION_RANGE
1571 MCALC_MOVE1 internal:
Movement
calculator can find no
solution
internal
1572 MCALC_MOVE2 internal:
Movement
calculator can find no
solution
internal
1573 MCALC_MOVE3 internal:
Movement
calculator can find no
solution
internal
1611 ERR_ILLEGAL_
ERRORCODE
Invalid error code to be
reported
internal
1911 COMMAND_IS_
RUNNING
Command can not be
executed, as another
command is currently
being processed
internal
1912 HIGH_PRIO_
COMMAND_IS_
RUNNING
Command can not be
executed, as another
command of higher
priority is currently
being processed
internal
1931 PARTMODL_
LIMITSWITCH
Command can not be
executed, as a limit
switch is active
Move drive away from limit
switch
2811 KBUS
internal
internal
*
2821 CFG_FACTORY_
LOAD
A Factory_Default data
set has been copied for
upload to RAM
A CONFIG_RESTORE
command has been
executed without a warm
start. The module is not
operational is this state.
Conduct a warm start or
Power-on reset
2831 MEASURE_ERR1 internal:
Unknown
hardware
internal