Overview of Error Blink Codes
•
207
Auxiliary
Commands
WAGO-I/O-SYSTEM 750
I/O Modules
3.3.1 Overview of Error Blink Codes
Error
No.
Name
Description
Possible cause/Remedy
1111 CI_UNKNOWN
COMMAND
INT
1112 CI_UNKNOWN
COMMAND2
Unknown command
A Drive command was
received with an unknown
command. Check command
(and possibly the move
program)
1113 CI_ERR1
Unknown
command,
like Error 1112
Same as for Error 1112
1114 CI_NOT
IMPLEMENTED
Command not
implemented
Command has been
prepared but has not (yet)
been implemented,
otherwise same as Error
1112
1115 CI_COMMAND_
DENIED
Could not execute
command
It was not possible to
execute a command, as the
marginal conditions do not
permit it. (incorrect mode,
incorrect parameter, .... for
this command)
1116 CI_SPEED1
Configuration:
Invalid
maximum frequency
Unacceptable value
specified for maximum
frequency
1117
CI_SPEED2
Invalid frequency value Unacceptable value
specified for set frequency
1118 CI_SPEED3
internal
1121 CI_ACC1
Invalid
acceleration
value
Check the specified
acceleration value
(configuration, Move
program, process data ….)
1122 CI_ACC2
Invalid
acceleration
value
Same as for Error 1121
1123 CI_
ROUNDARYSHAFT
_
SETPOINT
Operation with rotary
shaft: absolute position
setpoint output of rotary
shaft range
During operation with the
rotary shaft, the absolute
position must lie within the
range 0 …
RotaryShaftRange. Check
the position data and
parameters for the rotary
shaft.
1124
CI_POS_TABLE
Invalid table selected for
positioning to position
table
Check Parameter 2 for a
command "MOVE_L"