TITANUS
MICRO·SENS
®
Design
06/13
75
The following modules may optionally be used with the corresponding set-
tings for class B or A:
▪ Detection unit DM-TM-10 – with a sensitivity of 0.1 % LT/m to 0.6 %
LT/m
▪ Detection unit DM-TM-50 – with a sensitivity of 0.5 % LT/m to 0.6 %
LT/m
Possible system parameters:
▪ I- pipe system
– ≥ 9 V fan voltage, max. 40 m overall pipe length
▪ U- pipe system
– ≥ 9 V fan voltage, max. 50 m overall pipe length
▪ M- pipe system
– ≥ 9 V fan voltage, max. 50 m overall pipe length
▪ Double U- pipe system
– ≥ 9 V fan voltage, max. 50 m overall pipe length
Results: