TITANUS
MICRO·SENS
®
Design
06/13
99
NOTICE
The higher figure of the total current calculated (I
total
) is used to design the
power supply!
The power consumption of the TITANUS
®
can be found in Chapter, "Techni-
cal Data".
The maximum line length results from the permitted line drop on the feed.
The permitted line drop is the difference resulting from the stand-by accus
discharge voltage (21.5 V) and the lower operating voltage limit of the aspi-
ration smoke detection system.
2
max
total
I
A
U
L
Lmax
=
Maximum line length in [m]
A =
Wire cross-section in [mm²]
Itotal
=
Total current of the aspiration smoke detection system in [A]
γ
=
Conductivity: Cu=57m/
Ω
mm²
∆
U
=
Max.line drop on the feed
To guarantee the tightness of the housing seal, the appropriate cable
throughput for the particular cable must be selected.
▪ M 25- cable throughput: ∅ 9 to 14 mm
▪ M 20- cable throughput: ∅ 8 to 12 mm
The nominal capacity is calculated by means of the following formula:
25
.
1
)
5
.
0
(
min
h
I
t
n
I
K
total
quiescent
al
no
Knominal
=
nominal capacity of the emergency supply accumulators [Ah]
t =
required bridging time [h]
The factor 1.25 in the equation is only to be observed if bridging times are
smaller equal to [sic] 24 hours.
Line calculation
Emergency Supply
Calculation
Summary of Contents for Titanus Micro-Sens
Page 1: ...Air sampling smoke detection system Fire Detection TITANUS MICRO SENS Technical Manual ...
Page 2: ......
Page 4: ......
Page 12: ......
Page 16: ......
Page 24: ......
Page 74: ...Design TITANUS MICRO SENS 74 06 13 ...
Page 100: ......
Page 140: ......
Page 164: ......
Page 177: ...TITANUS MICRO SENS Commissioning 06 13 177 ...
Page 186: ......
Page 202: ......
Page 204: ......
Page 210: ......
Page 226: ......
Page 228: ......
Page 234: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e DOC Data 01 09 ...
Page 235: ......
Page 236: ......
Page 237: ...TITANUS MICRO SENS 06 13 ...
Page 238: ...TITANUS MICRO SENS ...