Installation
TITANUS
MICRO·SENS
®
102
06/13
Installation site
Fitting the TITANUS
®
When choosing the installation site, ensure that the notices can be easily
seen.
NOTICE
When choosing the installation site, ensure that it is not within a space
where doors open.
Figure 59: Installation of TITANUS
®
Ensure that the air outlet from the aspirating smoke detector is not blocked.
Maintain a distance of at least 10 cm between the air outlet from the TITA-
NUS
MICRO·SENS
®
and surrounding objects (e.g. wall).
If the TITANUS
MICRO·SENS
®
is installed with the aspiration pipe under-
neath, ensure that no foreign bodies or drops of water can get into the air
6.2
6.2.1
Aspiration
from above
Aspiration
from below