TITANUS
MICRO·SENS
®
Design
06/13
81
M-Pipe system
Figure 45: M-Pipe system for area protection
min. distance TITANUS
®
– T piece
2 m
max. distance TITANUS
®
– T piece
20 m
max. branch length
16.5 m
max. overall pipe length per pipe system
pipe
∅
25 mm plus
pipe
∅
12 mm
50 m
8 x 3 m
max. overall pipe length per pipe system per
with high fan voltage 9,0 V
pipe
∅
25 mm plus
pipe
∅
12 mm
40 m
6 x 3m
min. distance between 2 aspiration apertures (d)
4 m
max. distance between 2 aspiration apertures (d)
10 m
max. number aspiration apertures (n) per pipe system
6 no.
Number of apertures
3
6
Aspiration apertures
∅
in mm*
A
B
5,0
—
3,6
3,8
*) Press cut diameter in aspiration-reducing film sheet
Trigger Thresholds M-Pipe system
Number of apertures
2
6
1 blocked aperture
±25 %
±10 %
2 blocked apertures
O
±25 %
3 blocked apertures
O
O
4 blocked apertures
O
O
5 blocked apertures
O
O
6 blocked apertures
O
O
… is/are recognised when main air flow set x %
5.3.1.3
1 Pipe system
Limit values
Aspiration apertures
Summary of Contents for Titanus Micro-Sens
Page 1: ...Air sampling smoke detection system Fire Detection TITANUS MICRO SENS Technical Manual ...
Page 2: ......
Page 4: ......
Page 12: ......
Page 16: ......
Page 24: ......
Page 74: ...Design TITANUS MICRO SENS 74 06 13 ...
Page 100: ......
Page 140: ......
Page 164: ......
Page 177: ...TITANUS MICRO SENS Commissioning 06 13 177 ...
Page 186: ......
Page 202: ......
Page 204: ......
Page 210: ......
Page 226: ......
Page 228: ......
Page 234: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e DOC Data 01 09 ...
Page 235: ......
Page 236: ......
Page 237: ...TITANUS MICRO SENS 06 13 ...
Page 238: ...TITANUS MICRO SENS ...