Installation Pipe System
TITANUS
MICRO·SENS
®
158
06/13
Noise suppressor
C
TITANUS
MICRO·SENS
®
SD-1
Figure 100: Mounting of noise suppressors
1. Pass the pipe (∅ 25 mm) through the opened feed-through in the protec-
tion grid and fix it with the existing pipe collar in the air outlet of TITA-
NUS
®
. As the air return pipe fits exactly into the exit air opening, a tight
fit is ensured.
2. In order to connect the aspiration pipe with the noise suppressor please
insert the aspiration pipe into the designated pipe connectors of the
noise suppressor.
3. When installing the absorbing duct, ensure that the direction of air flow is
shown at the side of the housing’s bottom part.
4. Screw the bottom part of the housing directly to the wall.
NOTICE
Never use glue to connect the air sampling pipe and pipe connectors.
If severe variations in temperature are expected, then it is required to fix
the pipe right before the air filter in order to avoid elongation ( See chapter
installation of the pipe system “Linear expansion of the pipe system” ) of
the pipe and therefore possible loss of pipe connectivity (pipe contraction).
Noise suppressor
Cylinder or flat-head screws
– thread diameter: max. 4 mm
– head diameter: 5 to 7 mm
7.8
Installation material
Summary of Contents for Titanus Micro-Sens
Page 1: ...Air sampling smoke detection system Fire Detection TITANUS MICRO SENS Technical Manual ...
Page 2: ......
Page 4: ......
Page 12: ......
Page 16: ......
Page 24: ......
Page 74: ...Design TITANUS MICRO SENS 74 06 13 ...
Page 100: ......
Page 140: ......
Page 164: ......
Page 177: ...TITANUS MICRO SENS Commissioning 06 13 177 ...
Page 186: ......
Page 202: ......
Page 204: ......
Page 210: ......
Page 226: ......
Page 228: ......
Page 234: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e DOC Data 01 09 ...
Page 235: ......
Page 236: ......
Page 237: ...TITANUS MICRO SENS 06 13 ...
Page 238: ...TITANUS MICRO SENS ...