Aspiration reduction clips
Figure 25: Air flow reducer for dirty areas and deep freeze storage
The air sampling points, when used in areas where blockages can occur, are
equipped with a patented plastic clip, type AK-C, and a patented flexible air
flow reducer, type AK-x.
When used in deep freeze areas, the flexible air flow reducer near the air
sampling points expands and the ice is blasted off during blow-through. The
special plastic clip ensures that the air flow reducer remains in place.
For designs in areas requiring a blow-through system (e.g. dusty), air flow
reducers with plastic clips are used rather than aspiration-reducing film
sheets with marking tapes, because the openings can be blown clear more
easily. The plastic clips are more resistant at high pressures and can be
cleaned more effectively due to the rubber core.
3.3.2.2