TITANUS
MICRO·SENS
®
Installation
06/13
135
Delay time for air flow fault
If you want to change the delay time for forwarding an air flow fault, this can
be done by using the diagnostic tool for TITANUS
MICRO·SENS
®
.
Fault
delay
Fault
delay
Standard
Settings
stages
Detection Unit
DM-TM-10
1 s – 60 min
100 s
1 s
Detection Unit
DM-TM-50
1 s – 60 min
100 s
1 s
The standard delay time setting is 100 seconds. In areas with time-limited
fault variables (e.g. air pressure oscillations), then depending on the duration
of the fault variables, other delay times should be set.
Action-Alarm Threshold
Action-Alarm threshold changes for „Fire alarm after ROOM·IDENT“ can be
carried out by the diagnostic tool for TITANUS
MICRO·SENS
®
.
Action
alarm
Action
alarm
Standard
Settings
stages
Detection Unit
DM-TM-10
10 – 80 %
60 %
1 %
Detection Unit
DM-TM-50
10 – 80 %
60 %
1 %
Default value for action-alarm threshold is set to 60% of the fire alarm
threshold.
6.12.1.4
6.12.1.5
Summary of Contents for Titanus Micro-Sens
Page 1: ...Air sampling smoke detection system Fire Detection TITANUS MICRO SENS Technical Manual ...
Page 2: ......
Page 4: ......
Page 12: ......
Page 16: ......
Page 24: ......
Page 74: ...Design TITANUS MICRO SENS 74 06 13 ...
Page 100: ......
Page 140: ......
Page 164: ......
Page 177: ...TITANUS MICRO SENS Commissioning 06 13 177 ...
Page 186: ......
Page 202: ......
Page 204: ......
Page 210: ......
Page 226: ......
Page 228: ......
Page 234: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e DOC Data 01 09 ...
Page 235: ......
Page 236: ......
Page 237: ...TITANUS MICRO SENS 06 13 ...
Page 238: ...TITANUS MICRO SENS ...