Design
TITANUS
MICRO·SENS
®
90
06/13
TIP
If the maximum distance is exceeded a correction by an additonal aspira-
tion aperture on a branch pipe can be done. In this connection please no-
tice that two aspiration apertures in total can be projected on each branch
pipe.
NOTICE
When the fire location (ROOM·IDENT) localization must only be one aspi-
ration aperture per branch pipe can are projected. At least 3m distance
must be maintained between the suction port of the first branch pipe and
each configured subsequent aspiration aperture.