TITANUS
MICRO·SENS
®
Design
06/13
87
Double U-pipe system
Figure 50: Double U-pipe system, e.g. for equipment protection
min. distance TITANUS
®
– T piece
2 m
max. distance TITANUS
®
– T piece
20 m
max. branch length
12.5 m
max. overall pipe length per pipe system
pipe
∅
25 mm plus
pipe
∅
12 mm
50 m
8 x 3 m
max. overall pipe length per pipe system per
with high fan voltage 9,0 V
pipe
∅
25 mm plus
pipe
∅
12 mm
40 m
8 x 3m
max. number aspiration apertures (n) per pipe system
8 no.
min. distance between 2 aspiration apertures (d)
0.1 m
max. distance between 2 aspiration apertures (d)
4 m
Number of apertures
4
8
Aspiration apertures
∅
in mm*
4,4
3,0
*) Press cut diameter in aspiration-reducing film sheet
5.3.2.4
1 Pipe system
Limit values
Aspiration apertures