Technical Description
TITANUS
MICRO·SENS
®
46
06/13
Ceiling duct for concealed mounting
Figure 26: Ceiling feed-through for ceiling voids
If a hidden installation is required for monitoring of the pipe system, it can be
installed in the ceiling void. The ceiling feed through are put in the false ceil-
ing. According to the pipe design guidelines the ceiling feed-through are
equipped with aspiration-reducing film sheets with defined air sampling
points (see chapter Design "Pipe Design") and are connected to the pipe
system with air sampling hoses.
If the maximum length of these hoses is 1 m, refer to the pipe design de-
scribed in chapter "Design". If - due to construction - hose lengths of more
than 1 m are required, the air sampling pipe system must be calculated
separately (calculation is made by WAGNER).
The ceiling feed through is applicable for false ceiling panels with a thickness
of up to approximately 35 mm. The aspiration-reducing film sheets are avail-
able in two colours (pure white, RAL 9010 and papyrus white, RAL 9018)
and come ins special colours if required.
3.3.3
Aesthetics
Summary of Contents for Titanus Micro-Sens
Page 1: ...Air sampling smoke detection system Fire Detection TITANUS MICRO SENS Technical Manual ...
Page 2: ......
Page 4: ......
Page 12: ......
Page 16: ......
Page 24: ......
Page 74: ...Design TITANUS MICRO SENS 74 06 13 ...
Page 100: ......
Page 140: ......
Page 164: ......
Page 177: ...TITANUS MICRO SENS Commissioning 06 13 177 ...
Page 186: ......
Page 202: ......
Page 204: ......
Page 210: ......
Page 226: ......
Page 228: ......
Page 234: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e DOC Data 01 09 ...
Page 235: ......
Page 236: ......
Page 237: ...TITANUS MICRO SENS 06 13 ...
Page 238: ...TITANUS MICRO SENS ...