TITANUS
MICRO·SENS
®
Installation Pipe System
06/13
159
3-Way ball valve
Figure 101: Installation of 3-way ball valve
The ball valve is used for blowing through with compressed air (preferably)
or pressed air. Switching occurs between detection (position 0º) and blow-
through (position 180º). Connect the ball valve to the pipe system via reduc-
ing screw-joints.
NOTICE
Pressed air is compressed, non-purified surround air, containing humidity.
Compressed air is purified and de-humidified. If device and the pipe system
are located in areas below freezing, compressed air must be used for blow-
through.