TITANUS
MICRO·SENS
®
Installation Pipe System
06/13
149
Ceiling lead through
Ceilings feed-through for false ceiling
Figure 92: Installation of ceilings feed-through
To install the ceiling feed-through use the following steps:
1. Before gluing remove dirt and grease with the recommended cleaner.
2. Glue the hose connector to the corresponding T-piece with Tangit glue.
3. For each ceiling feed-through drill a hole of ・ 13mm through the false
ceiling.
4. Install the lead-through by first removing the nut, pushing the hose
sleeve from the bottom through the bore hole and then re-placing and
tightening the nut above the false ceiling.
5. Determine the required length and cut the air sampling hose. Attach the
hose to the sleeve of the ceiling feed-through and the hose connector at
the T-piece of the air sampling pipe. If necessary soften the hose ends
with a hot air fan.
7.4
7.4.1