Design
TITANUS
MICRO·SENS
®
76
06/13
Aperture diameter
The aperture diameters of the aspiration apertures can be found in the cor-
responding table for the respective pipe configuration:
Figure 39: I-pipe system
Number of apertures
1
2
3
4
5
Aspiration aperture
∅
in mm*
A
B
C
D
E
6,8
—
—
—
—
5,0
5,0
—
—
—
4,2
4,2
4,4
—
—
3,4
3,6
3,8
4,4
—
3,0
3,2
3,4
3,6
4,4
*) Press cut diameter in aspiration-reducing film sheet
Figure 40: U-pipe system
Number of apertures
2
4
6
8
Aspiration aperture
∅
in mm*
A
B
C
D
6,0
—
—
—
4,2
4,6
—
—
3,4
3,4
4,4
—
3,0
3,0
3,6
4,0
*) Press cut diameter in aspiration-reducing film sheet
5.2.4
I-pipe
Aspiration apertures
U-pipe
Aspiration apertures