INSTALLATION AND MAINTENANCE INSTRUCTIONS

HD101B

Conventional Photoelectric Smoke Detector             
                                                

Before Installing

NOTICE

: This manual should be left with the owner/user of this equipment.

IMPORTANT

: This detector used with the HD10X base must be tested and maintained regularly following NFPA 72

requirements. The detector should be cleaned at least once a year.

General Description

This detector can be used in all areas where photoelectric smoke detector is required. It is suited for fires ranging from
smoldering to flaming fires. 
This detector uses a state of-the-art optical sensing chamber, it is designed to provide open area protection and to be used
with most conventional fire alarm control panel. 
Two LEDs on each detector provide local 360° visible for indication of status. In the normal condition the LEDs flash
red every 5 seconds. When the detector senses smoke goes into pre-alarm sensitivity the LEDs will flash red every 1
second. When the detector senses smoke and goes into alarm the LEDs will latch on red.
The alarm can be reset only by a momentary power interruption. 

Base Terminals

No.

                

Function

1                  Remote Indicator (-)
2                  Power (-), In
3                  Power (-), Out
4                  Power (+), Remote Indicator (+)

Specifications

Operating Voltage Range:

       16 to 28VDC Volts Non-polarized

Standby Current:

               60µA @ 28 VDC(Maximum)

Alarm Current (LED on: )          30mA @ 28 VDC(Maximum)
Adjustable Sensitivity:             0.1 to 0.3dB/m
Operating Temperature Range:

   14°F to 122°F (-10°C to50°C)

Operating Humidity Range:        10% to 93% Relative Humidity, Non-condensing
Height:                        2.2˝ (55 mm) installed in Base
Diameter:

                       4.0˝ (103 mm)

Weight:                        5.5 oz. (155 g) 
Color & Material                 White/ ABS 
Bases                          HD10X
Compatible control panels          Conventional fire alarm control panel

Installation Guidelines (See Figure 2) 

All wiring must be installed in compliance with the local codes having jurisdiction. Proper wire gauges should be used.
The conductors used to connect smoke detectors to control panels and accessory devices should be color-coded to reduce
the likelihood of wiring errors. Improper connections can prevent a system from responding properly in the event of a
fire.
For signal wiring (the wiring between interconnected detectors), it is recommended that the wire be no smaller than 1.0
square mm. Wire sizes up to 2.5 square mm may be used with the base. For best system performance. The Power (+) and

HLogic Security Technology Co., Ltd 

   www. hstfire .com   Document Ref: M1115-04   Issue: 5.3     07/2015

  