TITANUS
MICRO·SENS
®
Maintenance
06/13
195
Pipe system blow through process
Figure 112: Lever position on the ball valve
The pipe system manual blow through process should be conducted in the
following stages:
1. Connect the compressed air supply needed for free-blowing the pipe
system (compressor or mobile free-blow device) via the quick release
coupling muff to the 3-way muff ball valve on the pipe system to be
blown through.
2. Separate the pipe system to be blown through by the 3-way muff ball
valve from the corresponding device, by moving the ball valve lever from
the 0° operating position to the 180° position (see Figure "Lever position
on the ball valve").
3. Blow the pipe system free manually for about 10 seconds.
4. Put the ball valve lever into the 90° position. In this position, the device
cannot be connected either to the pipe system or the compressed or
pressed air supply connection. Wait about 20 seconds so that the dust
and dirt stirred up in the pipe system can settle and thus not be aspirated
via the air sampling smoke detection system.
9.8
Summary of Contents for Titanus Micro-Sens
Page 1: ...Air sampling smoke detection system Fire Detection TITANUS MICRO SENS Technical Manual ...
Page 2: ......
Page 4: ......
Page 12: ......
Page 16: ......
Page 24: ......
Page 74: ...Design TITANUS MICRO SENS 74 06 13 ...
Page 100: ......
Page 140: ......
Page 164: ......
Page 177: ...TITANUS MICRO SENS Commissioning 06 13 177 ...
Page 186: ......
Page 202: ......
Page 204: ......
Page 210: ......
Page 226: ......
Page 228: ......
Page 234: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e DOC Data 01 09 ...
Page 235: ......
Page 236: ......
Page 237: ...TITANUS MICRO SENS 06 13 ...
Page 238: ...TITANUS MICRO SENS ...