Special project planning
Project planning for individual aperture monitoring
The following system parameters apply to the detection of an individual or a
particular number of blocked aspiration apertures, depending on pipe con-
figuration.
The specifications according to Chapter „Planning“ apply to project planning.
The following limit values and aperture diameters should also be taken into
account. Additional accessories (air filters, condensation separators, etc.)
can influence the maximum pipe length.
I-Pipe system
Figure 43: I-Pipe system for area protection
min. distance TITANUS
®
– 1st aspiration aperture
2 m
max. distance TITANUS
®
– 1st aspiration aperture
20 m
max. overall pipe length per pipe system
pipe
∅
25 mm plus
pipe
∅
12 mm
40 m
5 x 3 m
max. overall pipe length per pipe system per
with high fan voltage 9,0 V
pipe
∅
25 mm plus
pipe
∅
12 mm
30 m
5 x 3m
min. distance between 2 aspiration apertures (d)
4 m
max. distance between 2 aspiration apertures (d)
10 m
max. number aspiration apertures (n) per pipe system
5 no.
Number of apertures
1
2
3
4
5
Aspiration apertures
∅
in mm*
A
B
C
D
E
6,8
—
—
—
—
4,6
5,0
—
—
—
4,0
4,2
4,4
—
—
3,4
3,6
3,8
4,0
—
3,0
3,2
3,4
3,6
3,8
*) Press cut diameter in aspiration-reducing film sheet
5.3
5.3.1
5.3.1.1
1 Pipe system
Limit values
Aspiration apertures
Summary of Contents for Titanus Micro-Sens
Page 1: ...Air sampling smoke detection system Fire Detection TITANUS MICRO SENS Technical Manual ...
Page 2: ......
Page 4: ......
Page 12: ......
Page 16: ......
Page 24: ......
Page 74: ...Design TITANUS MICRO SENS 74 06 13 ...
Page 100: ......
Page 140: ......
Page 164: ......
Page 177: ...TITANUS MICRO SENS Commissioning 06 13 177 ...
Page 186: ......
Page 202: ......
Page 204: ......
Page 210: ......
Page 226: ......
Page 228: ......
Page 234: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e DOC Data 01 09 ...
Page 235: ......
Page 236: ......
Page 237: ...TITANUS MICRO SENS 06 13 ...
Page 238: ...TITANUS MICRO SENS ...