TITANUS
MICRO·SENS
®
Design
06/13
89
figure must be copied to every single sampling branch of other pipe forms
(U, M, double-U pipe system).
Referring to the project planning with burs please notice that the “critical
length” (l
krit.
)of a project planning does not exceed the maximum total length
of pipe respectively of branch (referring to U, M, double-U pipe system). The
critical length described the sampling point which is located most distantly
from TITANUS
®
.
Two aspiration apertures in total can be projected on each branch pipes at
which the minimal and maximum distance between the aspiration apertures
must be respected.
The opening diameters are valid for the projected aspiration apertures in ac-
cordance with the chapter „Opening diameter for standard project planning“.
Figure 52: Distances of apertures with branch pipes
The distance between the T-piece and the following branch pipe as well as
the pipe length between aspiration apertures on the branch pipes must not
exceed 12 m in total.
Figure 53: Maximum branch pipe
The length of pipe between the last T-piece and the last aspiration apertures
is the length of branch pipe. All other branch pipes need to be shorter. Two
aspiration apertures in total can be projected on each branch pipe.
Opening diameter
Distances of apertures
Maximum length of branch
pipe
Summary of Contents for Titanus Micro-Sens
Page 1: ...Air sampling smoke detection system Fire Detection TITANUS MICRO SENS Technical Manual ...
Page 2: ......
Page 4: ......
Page 12: ......
Page 16: ......
Page 24: ......
Page 74: ...Design TITANUS MICRO SENS 74 06 13 ...
Page 100: ......
Page 140: ......
Page 164: ......
Page 177: ...TITANUS MICRO SENS Commissioning 06 13 177 ...
Page 186: ......
Page 202: ......
Page 204: ......
Page 210: ......
Page 226: ......
Page 228: ......
Page 234: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e DOC Data 01 09 ...
Page 235: ......
Page 236: ......
Page 237: ...TITANUS MICRO SENS 06 13 ...
Page 238: ...TITANUS MICRO SENS ...