Installation Pipe System
TITANUS
MICRO·SENS
®
154
06/13
Filter
Installation of air filter, type LF-AD-x
Figure 96: Spacing for bore holes on base of air filter housing
1. To connect to the air sampling pipe with the air filter, insert the air sam-
pling pipe in the provided pipe connectors of the filter.
2. When installing the filter, ensure that the direction of air flow is shown at
the side of the housing’s bottom part.
3. Screw the bottom part of the housing directly to the wall.
NOTICE
Never use glue to connect the air sampling pipe and pipe connectors.
If severe variations in temperature are expected, then it is required to fix
the pipe right before the air filter in order to avoid elongation ( see chapter
installation of the pipe system „Linear expansion of the pipe system“) of the
pipe and therefore possible loss of pipe connectivity (pipe contraction).
Air filter
cylinder or flat-head screws
– thread diameter: max. 4 mm
– head diameter: 5 to 7 mm
7.6
7.6.1
Air filter LF-AD-x
Installation Material
Summary of Contents for Titanus Micro-Sens
Page 1: ...Air sampling smoke detection system Fire Detection TITANUS MICRO SENS Technical Manual ...
Page 2: ......
Page 4: ......
Page 12: ......
Page 16: ......
Page 24: ......
Page 74: ...Design TITANUS MICRO SENS 74 06 13 ...
Page 100: ......
Page 140: ......
Page 164: ......
Page 177: ...TITANUS MICRO SENS Commissioning 06 13 177 ...
Page 186: ......
Page 202: ......
Page 204: ......
Page 210: ......
Page 226: ......
Page 228: ......
Page 234: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e DOC Data 01 09 ...
Page 235: ......
Page 236: ......
Page 237: ...TITANUS MICRO SENS 06 13 ...
Page 238: ...TITANUS MICRO SENS ...