To insure equal air intake for all aspiration holes the following rules must be
obeyed:
▪ The length of the shortest and longest branch must not exceed a ratio of
1:2.
▪ The number of aspiration holes of the corresponding branches must not
exceed a ratio of 1:2.
▪ The aspiration holes should be evenly distributed on the corresponding
branches.
NOTICE
Each connected pipe system must comply with the design limits of TITA-
NUS
®
for the selected pipe design (please refer to chapter “Project Plan-
ning Limits”):
Figure 37: Example of a symmetrical and an asymmetrical U-pipe system
Figure „Example of a symmetrical and an asymmetrical U-pipe system” illus-
trates exemplary a U-shape pipe system with symmetrical and asymmetrical
pipe designs and according to chapter ´Standard Design´ the calculated di-
ameters of the aspiration holes. The diameters of the aspiration holes are
determined for each branch of the pipe system separately and are depend-
ent on the total number of aspiration holes of the respective branch. Please
refer to chapter “Hole diameters” for corresponding tables with hole diame-
ters.
Symmetry of the pipe system
Summary of Contents for Titanus Micro-Sens
Page 1: ...Air sampling smoke detection system Fire Detection TITANUS MICRO SENS Technical Manual ...
Page 2: ......
Page 4: ......
Page 12: ......
Page 16: ......
Page 24: ......
Page 74: ...Design TITANUS MICRO SENS 74 06 13 ...
Page 100: ......
Page 140: ......
Page 164: ......
Page 177: ...TITANUS MICRO SENS Commissioning 06 13 177 ...
Page 186: ......
Page 202: ......
Page 204: ......
Page 210: ......
Page 226: ......
Page 228: ......
Page 234: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e DOC Data 01 09 ...
Page 235: ......
Page 236: ......
Page 237: ...TITANUS MICRO SENS 06 13 ...
Page 238: ...TITANUS MICRO SENS ...