Design
TITANUS
MICRO·SENS
®
92
06/13
Figure 55: Duct direction change without baffle plates
Figure 56: Sound dampers in a duct
When a pipe system is built into air conditioning ducts, the following must be
observed:
▪ As the TITANUS
®
and the pipe system are in different pressure areas,
there must be an air return arrangement (see following page).
▪ The pipe entries into the duct must be sealed air-tight.
▪ The part of the pipe system which is outside the duct must be bonded
air-tight.