
Installation
TITANUS
MICRO·SENS
®
114
06/13
Incorporating the reset and isolating button
board
If a reset or isolating button is needed, the plate must be fitted into an addi-
tional housing.
Figure 70: Incorporating the reset and isolating board into the housing
Proceed as follows to incorporate the reset and isolating button board:
1. Using a screwdriver, loosen the four screws on the additional housing
cover.
2. Push the spacer blocks into the installation board (for fixing points see
Figure "Arrangement of holes on the installation plate of the additional
housing") on the additional housing. The reset and isolating button board
is then engaged with the spacer blocks using the holes provided.
3. Feed the wires through as per the following switching plan.
4. Fit the cover again, using a screwdriver to fit the four screws on the de-
vice cover firmly.
6.6
Fitting
Summary of Contents for Titanus Micro-Sens
Page 1: ...Air sampling smoke detection system Fire Detection TITANUS MICRO SENS Technical Manual ...
Page 2: ......
Page 4: ......
Page 12: ......
Page 16: ......
Page 24: ......
Page 74: ...Design TITANUS MICRO SENS 74 06 13 ...
Page 100: ......
Page 140: ......
Page 164: ......
Page 177: ...TITANUS MICRO SENS Commissioning 06 13 177 ...
Page 186: ......
Page 202: ......
Page 204: ......
Page 210: ......
Page 226: ......
Page 228: ......
Page 234: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e DOC Data 01 09 ...
Page 235: ......
Page 236: ......
Page 237: ...TITANUS MICRO SENS 06 13 ...
Page 238: ...TITANUS MICRO SENS ...