TITANUS
MICRO·SENS
®
Commissioning
06/13
171
Air Pressure-Independent Adjustment
Air pressure-independent adjustment for the TITANUS
MICRO·SENS
®
hap-
pens completely automatically each time the detection unit is inserted into
the device base and the Jumper X4 is changed or via the diagnostics tool.
During the learning phase, the alarm detection is fully functional. During this
time the operating display flashes and there must be no air flow influences.
When initialising is completed, the operating display changes to a permanent
light and the air flow sensor has determined its ideal value for the connected
pipe system.
Air Pressure-Dependent Adjustment
This kind of adjustment can only be carried out by using the diagnostics tool.
A barometer (Recommended: Digital precision pocket barometer GPB 1300,
Greisinger electronic GmbH) is required for air pressure-dependent adjust-
ment of the air flow sensor. The following steps must be taken:
1. Press the “Settings” button so that you can change the figures in the di-
agnostics tool on the “Settings” screen.
8.3.1
8.3.2
Summary of Contents for Titanus Micro-Sens
Page 1: ...Air sampling smoke detection system Fire Detection TITANUS MICRO SENS Technical Manual ...
Page 2: ......
Page 4: ......
Page 12: ......
Page 16: ......
Page 24: ......
Page 74: ...Design TITANUS MICRO SENS 74 06 13 ...
Page 100: ......
Page 140: ......
Page 164: ......
Page 177: ...TITANUS MICRO SENS Commissioning 06 13 177 ...
Page 186: ......
Page 202: ......
Page 204: ......
Page 210: ......
Page 226: ......
Page 228: ......
Page 234: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e DOC Data 01 09 ...
Page 235: ......
Page 236: ......
Page 237: ...TITANUS MICRO SENS 06 13 ...
Page 238: ...TITANUS MICRO SENS ...