Technical Description
TITANUS
MICRO·SENS
®
50
06/13
In order to extend the maintenance intervals, one air filter can be installed in
every output pipe instead of one air filter inside the main sampling pipe. The
same design specifications shall apply as stated in the projection tables in
the appendix.
LF-AD
LF-AD
LF-AD
LF-AD
TITANUS
®
Figure 31: LF-AD filter in the main sampling pipe
Furthermore, in order to extend the maintenance intervals, several air filters
can be installed in parallel in the main sampling pipe. This requires the main
sampling pipe to be split into one or several pipes and to be equipped with
the same air filter or the combination of air filters. The individual pipes can
then alternatively be either combined again to one main sampling pipe or be
separately continued into the monitoring area(s). The same design specifica-
tions for the individual air filters shall apply as stated in the projection tables
in the appendix.
Summary of Contents for Titanus Micro-Sens
Page 1: ...Air sampling smoke detection system Fire Detection TITANUS MICRO SENS Technical Manual ...
Page 2: ......
Page 4: ......
Page 12: ......
Page 16: ......
Page 24: ......
Page 74: ...Design TITANUS MICRO SENS 74 06 13 ...
Page 100: ......
Page 140: ......
Page 164: ......
Page 177: ...TITANUS MICRO SENS Commissioning 06 13 177 ...
Page 186: ......
Page 202: ......
Page 204: ......
Page 210: ......
Page 226: ......
Page 228: ......
Page 234: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e DOC Data 01 09 ...
Page 235: ......
Page 236: ......
Page 237: ...TITANUS MICRO SENS 06 13 ...
Page 238: ...TITANUS MICRO SENS ...