2. Release the 4.6 mm and the 4.2 mm aspiration holes on the test pipe
again.
3. Now click on the lower “Set“ button in the “Settings“ screen and start air
flow initialising by pressing the “Initialise“ button.
The fault messages and displays must go out. The “Initialising active“
field in the “Settings“ screen of the diagnosis tool flashes for the duration
of initialising.
4. After initialising, close the 4.2 mm aspiration hole on the test pipe with
some sticky tape.
After about 5 secs, the fault display on the device must start to flash.
After about 35 secs, the fault display on the device must be permanently
on. The device signals the fault “Air flow too low (statistical evaluation)“.
The air flow figure is about –35 %.
5. Open the 4.2 mm aspiration hole again.
After a few seconds, the fault display on the TITANUS
MICRO·SENS
®
must stop flashing.
6. Open the 7.0 mm aspiration pipe on the test pipe.
After about 5 secs the fault display on the device must start to flash.
After about 35 secs, the fault display on the device must be permanently
on. The device signals the fault “Air flow too high (statistical evaluation)“.
The air flow figure is about +85 %.
7. Close the 7.0 mm aspiration hole again.
The fault display on the TITANUS
MICRO·SENS
®
must stop flashing af-
ter a few seconds.
8. Remove the test pipe and re-connect the pipe system.
After function tests are completed, the original settings must be restored.
Commissioning the TITANUS
MICRO·SENS
®
is to be repeated from section
“Air Flow Sensor Adjustment“.
Test whether ...
1. The pipe system is firmly connected to the TITANUS
MICRO·SENS
®
pipe connection.
2. All pipe fittings are glued and the pipe system is sealed tight. For this,
first close all aspiration apertures (e.g. with insulating tape). Using a flow
measurement device, measure the air flow at the aperture for the air flow
return.
Connection testing
Summary of Contents for Titanus Micro-Sens
Page 1: ...Air sampling smoke detection system Fire Detection TITANUS MICRO SENS Technical Manual ...
Page 2: ......
Page 4: ......
Page 12: ......
Page 16: ......
Page 24: ......
Page 74: ...Design TITANUS MICRO SENS 74 06 13 ...
Page 100: ......
Page 140: ......
Page 164: ......
Page 177: ...TITANUS MICRO SENS Commissioning 06 13 177 ...
Page 186: ......
Page 202: ......
Page 204: ......
Page 210: ......
Page 226: ......
Page 228: ......
Page 234: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e DOC Data 01 09 ...
Page 235: ......
Page 236: ......
Page 237: ...TITANUS MICRO SENS 06 13 ...
Page 238: ...TITANUS MICRO SENS ...