INSTALLATION AND MAINTENANCE INSTRUCTIONS

Photoelectric Smoke Detector

2-Wire: 

2WTR-B (Form C Relay), 2WTA-B (Sounder)

4-Wire: 

4WTR-B (Form C Relay), 4WTA-B (Sounder)

 

4WTAR-B (Form C Relay, Sounder), 4WITAR-B (Isolated Thermal, Form C Relay, Sounder)

Series

Before Installing

Please  read  thoroughly  System  Sensor 

Applications  Guide  for  System 

Smoke  Detectors

,  which  provides  detailed  information  on  detector  spac-

ing, placement, zoning, wiring, and special applications. Copies are avail-
able on System Sensor’s web site: www.systemsensor.com.

NOTICE:

 This manual shall be left with the owner/user of this equipment.

IMPORTANT: 

This  detector  must  be  tested  and  maintained  regularly 

following  National  Fire  Protection  Association  (NFPA)  72  National 
Fire Alarm Code requirements. At a minimum, cleaning should be per-
formed annually.

General Description

Models  2WTR-B  and  2WTA-B  are  2-wire  photoelectric  smoke  detectors; 
models  4WTR-B,  4WTA-B,  4WTAR-B,  and  4WITAR-B  are  4-wire  photo-
electric smoke detectors. All models incorporate a state-of-the-art optical 
sensing  chamber  and  an  advanced  microprocessor.  The  microprocessor 
allows the detector to automatically adjust its sensitivity back to the fac-
tory setting when it becomes more sensitive due to contaminants settling 
in  its  chamber.  In  order  for  this  feature  to  work  properly,  the  chamber 
must never be opened while power is applied to the smoke detector. This 
includes  cleaning,  maintenance  or  screen  replacement.  All  models  also 
feature a restorable, built-in, fixed temperature (135°F) thermal detector 
and are also capable of sensing a freeze condition if the temperature is 
below 41°F.
Models 2WTA-B, 4WTA-B, 4WTAR-B, and 4WITAR-B contain a piezoelec-
tric  horn  which  generates  the  ANSI  S3.41  temporal  pattern  in  an  alarm 
condition. All detectors on a zone will sound when the power supply to 
them is reversed. The RRS-MOD can be used for the power supply reversal 
function. The RRS-MOD also enables all the detectors’ sounders on a zone 
to be synchronized and allows the zone to be silenced from the panel by 
entering the alarm silence key at the keypad.
The detector that initiated the alarm condition will have its red LED and 
Form C relays (if applicable) latched until reset by panel.
The model 4WITAR-B photoelectronic smoke sensor is isolated from the 
fixed-temperature  heat  sensor,  providing  a  self-resetting,  local  audible 
smoke alarm that does not alarm at the panel. Only the fixed-temperature 
heat sensor will cause the 4WITAR-B to initiate an alarm at the panel and 
the relay to change its state.

NOTE:

 In order for all i

3

 sounder detectors on a loop to sound when the 

panel alarms, the supply voltage polarity must be reversed. A reversing 
relay, System Sensor model number RRS-MOD, must be used. The RRS-
MOD is designed to allow all i

3

 Series detectors in the same loop to sound 

when one of the detectors goes into alarm. In addition, the RRS-MOD will 
synchronize all of the i

3

 Series sounder smoke detectors on the loop. Some 

panels may require the use of programmable outputs. Refer to System Sen-
sor literature for further information on the RRS-MOD.
All i

3

 Series detectors are designed to provide open area protection. Two-wire 

models must be used with compatible UL Listed panels only.
When used with an “i

3

 Ready” control panel or the i

3

 Series 2W-MOD2 

module (refer  to  installation manual), the  2WTR-B  and  2WTA-B  are  ca-
pable of generating a “maintenance needed” signal. The 2W-MOD2 can 
indicate a need for cleaning, replacement, or a freeze trouble at the control 
panel or module.

WARNING

The 2W-MOD2 has replaced the previous model number 2W-MOD. To en-
sure proper remote maintenance signaling capabilities, do not use the 2W-
MOD with i

3

 model numbers 2WTR-B and 2WTA-B.

Installation  of  the  2WTR-B,  2WTA-B,  4WTR-B,  4WTA-B,  4WTAR-B,  and 
4WITAR-B detectors is simplified by the use of a mounting base that may 
be  pre-wired  to  the  system,  allowing  the  detector  to  be  easily  installed 
or  removed.  The  mounting  base  installation  is  further  simplified  by  the 
incorporation of features compatible with drywall fasteners.
Two LEDs on the detector provide a local visual indication of the detec-
tor’s status: 

Table 1: Detector LED Modes

Green LED

Red LED

Power-up

Blink 10 sec

Blink 10 sec

Normal (standby)

Blink 5 sec

Out of sensitivity

Blink 5 sec

Freeze Trouble

Blink 10 sec

Alarm

Solid

During an initial power-up delay, the red and green LEDs will blink syn-
chronously once every ten seconds. It will take approximately 80 seconds 
for the detector to finish the power-up cycle (see Table 2).

Table 2: Power-up Sequence for LED Status Indication*

Condition

Duration

Initial LED Status Indication

80 seconds

Initial LED Status Indication
(if excessive electrical noise is present)

4 minutes

* Refer  to  Electrical  Specifications  for  start-up  time  in  conjunction  with 

panel alarm verification.

NOTE:

  If,  during  power-up,  the  detector  determines  there  is  excessive 

electrical noise in the system such as those caused by improper ground-
ing of the system or the conduit, both LEDs will blink for up to 4 minutes 
before displaying detector status (see Table 2).
After  power-up  has  completed  and  the  detector  is  functioning  normally 
within  its  listed  sensitivity  range,  the  green  LED  blinks  once  every  five 
seconds. If the detector is in need of maintenance because its sensitivity 
has  shifted  outside  the  listed  limits,  the  red  LED  blinks  once  every  five 
seconds. When the detector is in the alarm mode, the red LED latches on. 
The LED indication must not be used in lieu of the tests specified under 
Testing. In a freeze trouble condition, the red LED will blink once every 10 
seconds (refer to Table 1).
To measure the detector’s sensitivity, the i

3

 Series Model SENS-RDR Infra-

red Sensitivity Reader tool (see Figure 4) should be used. Refer to instruc-
tions manual D100-98-00 for the proper use of the SENS-RDR.
Models 2WTR-B and 2WTA-B also include an output that allows an op-
tional Model RA400Z Remote Annunciator to be connected.

Mounting

General spacing guidelines are 30˝×30˝, with each detector covering 900 
ft

2

 under maximum conditions.

Consult NFPA 72, the local Authority Having Jurisdiction (AHJ), and/or 
applicable codes for specific information regarding the spacing and place-
ment of smoke detectors.
Each i

3

 Series detector is supplied with a mounting base that can be ceil-

ing- or wall-mounted:
1.  To a single gang box, or
2.  To a 3

1

2

-inch or 4-inch octagonal box, or

3.  To a 4-inch square box with a plaster ring, or
4.  Direct mount or to ceiling using drywall fasteners.

Summary of Contents for 2WTR-B

Page 1: ...e RRS MOD All i3 Series detectors are designed to provide open area protection Two wire models must be used with compatible UL Listed panels only When used with an i3 Ready control panel or the i3 Series 2W MOD2 module refer to installation manual the 2WTR B and 2WTA B are ca pable of generating a maintenance needed signal The 2W MOD2 can indicate a need for cleaning replacement or a freeze troubl...

Page 2: ...than 2 gauge apart under the same clamping plate Two Wire Compatibility System Sensor two wire smoke detectors are marked with a compatibility identifier located on the label on the back of the product For two wire models 2WTR B and 2WTA B connect detectors only to compatible alarm control panels as identified by System Sensor s two wire compatibility chart available at www systemsensor com NOTE M...

Page 3: ...ither of the thermistors Hold the heat source about 12 inches from the detector to avoid damage to the plastic NOTE For the above tests the detector will reset only after the power source has been momentarily interrupted It is not necessary to reset the model 4WITAR B when smoke is used to initiate the alarm When testing the 4WITAR B model pressing the test switch will result in a non latching loc...

Page 4: ... of the FCC Rules These limits are designed to pro vide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a parti...

Reviews: