background image

GAMEWELL-FCI

12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118

Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.

©2009 by Honeywell International Inc.   All rights reserved.

www.gamewell-fci.com

9020-0584 Rev. C page 1 of 2

1415

Description

The System Sensor 1451 ionization type smoke detectors
are specifically designed to meet the performance require-
ments of fire detection and fire alarm systems. The 1451
ionization detector uses a state-of-the-art, dual unipolar
sensing chamber. The detector is designed to provide
open area detection and when installed in a two-wire base
is compatible with Gamewell-FCI fire alarm control panels.
The detectors operation and sensitivity can be tested in
place.

The 1451 detector is built of plug-in construction and plugs
into the same base as the 2451 Series photoelectronic
smoke detectors, making both models interchangeable.
The bases are available for two-wire, four-wire, and 120
VAC four wire operation.

Two visible LEDs on each detector flash approximately
every ten seconds indicating that power is being applied to
the detector. The LEDs light steadily when the detector is
in alarm. A remote LED annunciator is available as an
optional accessory.

The 1451 detector is Listed for use inside ducts up to a
velocity of 1,200 FPM.

Sensitivity testing is performed by placing a test magnet
against the cover. The LED on the detector should light
within 5 seconds.

Field metering of detector sensitivity may be performed
with the aid of a voltmeter and Test Kit, MOD 400R.

Specifications

Nominal Sensitivity:

1.5 %/ft

Operating Voltage:

8.5 - 35 VDC (24 VDC nominal)     

Operating
Temperature:

32° to 120° F (0° to 49° C)

Operating Humidity:  

10 % - 93 % relative humidity

Air Velocity:

1,200 FPM

Altitude:

10,000 ft.

Construction:

Off-white flame retardant plastic

Diameter:

6.2 inches 

(15.7 cm)

Height:

3.2 inches 

(8.1 cm)

Weight:

0.5 lb (277 g)

Features

Uses a unique dual unipolar sensor that provides 
exceptional stability

Offers an easy plug-in of the head to base

Provides the following built-in features:
- Tamper-resistant
- Test switch
- Visual alarm indicators

Displays a 360° view angle of alarm LEDs

Compatible with the Gamewell-FCI fire alarm control 
panels

Performs field adjustable sensitivity and field metering 
of detector sensitivity

Furnishes insect-resistant screening (.020"/.508 mm 
openings)

Includes a removable insect screen and cover for field 
cleaning

Sealed against dirt, insects, and back pressure

System Sensor

Ionization Smoke Detector

1415

SIGNALING

FM

MEA

Approved

APPROVED

US LISTED

UL

C

R

An ISO 9000-2000 Company