Patented, U.S. Patent No. Des. 428,351; 6,380,846; 6,314,772; Other Patents Pending

Document 50964-1 

I56-2263-003

Description
The BG-12 pull station is a non-coded, dual-action manual pull station with a hex-lock reset 

feature. It provides Fire•Lite control panels with one normally open (N/O) alarm initiating 
input. The BG-12 meets the ADAAG controls and operating mechanisms guidelines (sec

-

tion 4.1.3[13]), and the ADA requirement for a 5 lb. maximum pull force to activate the pull 
station. Operating instructions are molded into the pull station handle along with Braille 
text. Molded Terminal numbers are also present.

Ratings 

Switch contact (N/O) is gold plated for reliability and rated at 0.25 A at 30 volts (AC or 
DC).

Installation

The BG-12 pull station can be surface mounted to an SB-10 or SB-I/O surface backbox or 
semi-flush mounted on a standard single-gang, double-gang or 4

 (10.16 cm) square electrical 

box. The optional BG-TR trim ring can be used if the BG-12 is to be semi-flush mounted.

Operation

To activate the dual-action pull station, push in and pull down on the handle. The word 

‘ACTIVATED’ appears after the handle is pulled down. This will remain until the pull sta

-

tion is reset.

The  pull  station  includes  one  Single  Pole,  Single Throw  (SPST)  Normally  Open  (N/O) 

switch which closes upon activation of the pull station.

Resetting the Pull Station
1. 

To reset the BG-12 hex lock pull station, insert the supplied 9/64-inch hex wrench into 
the lock until firmly seated and turn counterclockwise 1/4-turn

.

2.  Open the door until the handle returns to normal.
3.  Close and lock the door.

NOTE:

  Closing the door automatically resets the switch to the ‘Normal’ position. Open

-

ing the door will not activate or deactivate the alarm switch.

STRIP GAUGE

1        2       3      4

IDC –

FROM  

FACP +

TO NEXT

DEVICE

– IDC

+

WARNING: DO NOT LOOP WIRING 

UNDER ANY TERMINALS. BREAK WIRE 

RUN TO MAINTAIN IDC SUPERVISION.

P0205-00

Wiring

CAUTION! 

Do not detach the door of the pull station during installation. The door of 

the pull station cannot be reattached to the backplate after the backplate has already been 
installed onto an electrical box.

CAUTION!

Install  the  Fire•Lite  BG-12  pull  station  in  accordance  with  these  instructions, 

 

applicable NFPA standards, national and local Fire and Electrical codes and the requirements 
of the AHJ (Authority Having Jurisdiction). Regular testing of the devices should be con

-

ducted in accordance with the appropriate NFPA standards. Failure to follow these directions 
may result in failure of the device to report an alarm condition. Fire•Lite is not responsible for 

 

devices that have been improperly installed, tested or maintained.

ADA Compliance

For ADA compliance, if the clear floor space only allows forward approach to an object, the 
maximum forward reach height allowed is 48 inches (121.92 cm). If the clear floor space 
allows parallel approach by a person in a wheelchair, the maximum side reach allowed is 
54 inches (137.16 cm).

BG-12

Manual Pull Station

WARNING!  Do not loop wiring under any 

terminals. Break wire run to 
maintain IDC supervision.

Document 50964-1 

I56-2263-003

P0194-01