FB Speed Actual
ID865
Actual speed value send to fieldbus.
V1.25.3
FB Torque Reference %
ID 1140
Torque reference value from fieldbus
Default Control of FB PD 1
V1.25.4
FB Limit Scaling %
ID 46
Limit scaling input value from fieldbus.
Default Control of FB PD 2.
V1.25.5
FB Adjust Reference
%
ID 47
Reference adjustment value from fieldbus.
Default Control of FB PD 3.
V1.25.6
FB Analog Output
%
ID 48
Fieldbus value to control analogue output.
Default Control of FB PD 4.
V1.25.7
FB Motor Current
A
ID 45
Motor current (drive independent) given with one decimal point.
V1.25.8
Fault Word 1
ID 1172
Different faults are collected to two words that can be read from fieldbus or with
VACON
®
NCDrive PC software.
Fault Word 1 ID1172
Bit
Fault(s)
B0
F1 Over current, F31 IGBT, F41 IGBT
B1
F2 Over Voltage
B2
F9 Under Voltage
B3
F15 Motor Stalled
B4
F3 Earth Fault
B5
F17 Motor Underload
B6
F14 Unit Over Temperature
B7
F16 Motor Temperature, F29 Thermistor,
B8
F10 Input line fault
B9
F42 OR W42 Brake Resistor
B10
B11
F52 Keypad or F52 PC communication fault
B12
F53 FieldBus fault
B13
F59 System Bus fault
B14
F54 Slot Communication fault
B15
F50 4mA fault
V1.25.9
Fault Word 2
ID 1173