F45
Device added (default param.)
Possible cause:
1. Option board of different type added.
Correcting measures:
•
Reset
•
Set the option board parameters again.
F50
4mA supervision
Possible cause:
1. Current at the analogue input is below 4mA.
2. Signal source has failed
3. Control cable is broken or loose
Correcting measures:
•
Check the current loop circuitry.
F51
External fault
Possible cause:
1. Digital input fault.
Correcting measures:
•
Remove fault situation from external device.
F52
Keypad communication
Possible cause:
1. The connection between the control keypad or VACON
®
NCDrive and the AC drive is
broken.
Correcting measures:
•
Check keypad connection and possible keypad cable.
F53
Fieldbus communication Slot D
Possible cause:
1. The data connection between the fieldbus Master and the fieldbus board is broken.
2. Watch dog pulse is missing from fieldbus, also if missing from slot E.
Correcting measures:
•
Check installation.
•
If installation is correct contact the nearest VACON
®
distributor.
F54
Slot fault
Possible cause:
1. Defective option board or slot
Correcting measures:
•
Check board and slot.
•
Contact the nearest VACON
®
distributor.