7.6 Limit settings
7.6.1 Current limit handling
P2.6.1.1
Current limit
ID107
“Current Limit”
This parameter determines the maximum motor current from the AC drive. The
parameter
’s
value range differs from size to size.
When the current limit is active the drive output frequency is reduced until current is
below the set limit.
In closed loop control, the current limit affects the torque producing current limit, not the
total current. This can be changed in options group with the
“LimitTotalCurren
t
”
parameter.
In drive synch operation limiting is for average current of units.
P2.6.1.2
Scaling of current limit ID399
“Currnt Lim Sclng”
0
= Not used
1
= AI1
2
= AI2
3
= AI3
4
= AI4
5
= FB Limit Scaling ID46 Monitoring value
This signal will adjust the maximum motor current between 0 and the parameter Motor
Current Limit.
P2.6.3
Current Limit Kp
ID1451
P-gain of motor side over current controller
P2.6.4
Current Limit Ki
ID1452
I-gain of motor side over current controller