P2.16.10 Number of tries after underload fault trip
ID738
“Underload tries”
This parameter determines how many automatic fault resets can be made during the trial
time after underload trip.
0
= No automatic fault reset after Underload fault trip
>0
= Number of automatic fault resets after Underload fault trip
P2.16.11 Fault Simulation
ID1569
“Fault Simulation”
With this parameter it is possible to simulate the different faults without actually making,
for example, overcurrent situation. In drive interface point of view, the behaviour is
identical to actual fault situation.
B00
= +1 = Simulates over current fault (F1)
B01
= +2 = Simulates over voltage fault (F2)
B02 =
+4 = Simulates under voltage fault (F9)
B03 =
+8 = Simulates output phase supervision fault (F11)
B04 =
+16 = Simulates earth fault (F3)
B05 =
+32 = Simulates system fault (F8)
This fault simulation cover wide range of different faults in drive, see fault description
for details.
B06 =
+64 = Simulates encoder fault (F43)
B07 =
+128 = Simulates over temperature warning (W14)
B08 =
+256 = Simulates over temperature fault (F14)
Warning bit needs to be active that fault will come in simulation. If fault bit is left active
drive will go fault state at warning limit when drive temperature will rise to warning
level.
B09 =
+512 = Reserved
B10 =
+1024 = Simulates Fan Cooling fault (F32)