DATA LOGGER TRIGGER WORD
There is a special trigger word in application level that can be used to trigger data logger. This word
can be used for triggering when source is selected from Application and original VACON
®
Marine
application vcn is used. Variable is called
“DataLoggerTrigWord”
DataLoggerTrigWord ID97
Function
Comment
b0
Fault Status
Logger is triggered when there is a fault
b1
Warning Status
Logger is triggered when there is a warning
b2
Auto Reset Warning
Logger is triggered when there is a fault that
has been defined to be automatically reset.
This bit can be used to get the first fault
situation.
b3
Fault Status OR Warning Stattus
B0 OR B1 triggering situation has happened
b4
Fault Status OR Auto Reset Warning
B0 OR B2 triggering situation has happened
b5
b6
b7
b8
b9
b10
b11
b12
b13
b14
b15