164
• VACON®
apfiff09 marine
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
P2.5.6.3
Digital output 1 on-delay
ID487
“DO1 ON Delay”
P2.5.6.4
Digital output 1 off-delay
ID488
“DO1 OFF Delay”
P2.5.7.3
Digital output 2 on-delay
ID491
“DO2 ON Delay”
P2.5.7.4
Digital output 2 off-delay
ID492
“DO2 OFF Delay”
With these parameters you can set on- and off-delays to digital outputs.
Signal
DO
On
Delay
Off
Delay
Figure 7-11. Digital outputs 1 and 2, on- and off-delays
P2.5.6.5 Invert digital output 1 ID1587
“INV Delayed DO1”
P2.5.7.5 Invert digital output 2
ID1588 “INV Delayed DO2”
Inverts delayed digital output operation.
Signal
DO
On
Delay
Off
Delay
P2.5.6.6
ID.Bit Free DO 1
ID1217
P2.5.7.6
ID.Bit Free DO 2
ID1385
Select the signal for controlling the DO. The parameter has to be set in format xxxx.yy
where xxxx is the ID number of a signal and yy is the bit number. For example, the value
for DO control is
1174.02
. 1174 is the ID number of Warning Word 1. So the digital
output is ON when bit number 02 of the warning word (ID no. 1174) i.e.
Motor underload
is high.
Summary of Contents for apfiff09 marine
Page 1: ...vacon nx ac drives apfiff09 marine application manual ...
Page 2: ......
Page 310: ......