apfiff09 marine
VACON®
•
109
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public
7
= “DTC Ident” –
Dead Time Compensation identification
Current is applied to the motor but shaft will not be rotated.
This identification mode is needed for Sensorless control, Ident All can be used instead
of this.
Parameters updated during this identification
-
P 2.8.4.2 U/f Ratio Select
-
P 2.8.4.5 U/f Mid Freq
-
P 2.8.4.6 U/f Mid Voltg
-
P 2.8.4.7 Zero Freq Voltg
-
P 2.8.9.16 RsVoltageDrop
-
P 2.8.9.17 IrAddZeroPVoltag
-
P 2.8.9.20 LsVoltageDrop
-
P 2.8.9.22 IU Offset
-
P 2.8.9.23 IV Offset
-
P 2.8.9.24 IW Offset
-
P 2.8.9.25 Estimator Kp
-
P 2.8.9.27 VoltageDrop
-
P 2.8.9.29 FluxSaturatRatio
-
P 2.8.9.30 DeadTimeComp.
-
P 2.8.9.31 DeadTieContCurL
10 =
“ID Run Fails”
- Identification failed
Identification failed in last attempt.
P2.1.11
Motor Type
ID650
“Motor Type”
Select used motor type with this parameter
0
“Induction”
- Induction motor
- Asynchronous motor
1
“PMSM”
- Permanent magnet synchronous motor
- Synchronous Motor
- Contact factory before using with externally magnetized motor.
- If Switching Frequencies above 3.5 kHz are not needed, it is recommended to
change to Software Modulator 1 at this point. Read more details in Chapter 6.8.3
Permanent magnet synchronous motor setting and Chapter 8 Identification functions
for permanent magnet synchronous motors.
See related parameter in “G
2.8.6: Motor Control \
PMSM Control”.
2
“Sep.Ex SM” –
Separately Excited Synchronous Motor
- This application does not support excitation reference to excitation drive as of
18.1.2018.
3
“Reserved”
4
“SRM”