P2.12.10.4 FieldBus Response Slot E
ID733
“FB Fault Slot E”
Set here the response for a fieldbus fault if the active control place is fieldbus. For more
information, see the respective Fieldbus Board Manual.
0
= No response
1
= Warning
2
= Fault, stop mode after fault according to Stop Function
3
= Fault, stop mode after fault always by coasting
4
= Warning, Previous reference from 10 seconds. Forced fault after delay.
5
= Quick Stop, Action defined by P2.3.11.1 Quick Stop Mode is taken.
6
= Warning, Change control place to IO.
7.12.12
External Fault function
P2.12.11.1 Response to external fault
ID701
“External Fault 1”
P2.12.11.2 Response to external fault
ID747
“External Fault 2”
Defines the response to a digital input signal informing about an external condition where
the drive needs to react to. The external warning/fault indication can be connected to a
digital output.
0
= No response
1
= Warning
2
= Fault, stop mode after fault according to Stop Function
3
= Fault, stop mode after fault always by coasting